Description
-Input Type: J, K, T, N, R, S, B, E, Pt100, Pt1000, NTC and 0-50 mV
– Accuracy Typical:
Pt1000 / mV: 0.07 % span
Pt100: 0.08 % span
T/C: 0.07 % span ±1 °C (1.8 °F)
NTC: 0.2 °C (0.36 °F)
– Maximum:
Pt1000 / mV: 0.15 % span
Pt100: 0.15 % span
T/C: 0.15 % span ±1 °C (1.8 °F)
NTC: 0.45 °C (0.81 °F)”
– Output Type: 4-20 mA
– Output Resolution: 0.25 µA
– Thermal Drift: < 0.05 % / 25 °C (77 °F)
– Isolation Input-Output: 1.5 kVrms
– Electric Protection: Reverse Polarity
– HART® Version: HART V7, compatible with HART V5
– Configuration Interface: Through TxConfig-HRT adapter or HART®
certified HandHeld
– Configuration Software: TxConfig II
– Approvals / Regulations: CE, NAMUR NE43, RoHS, Reach, HART®
– Electromagnetic Compatibility
CISPR 11
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
– Operating Conditions: -40 to 85 °C (-40 to 185 °F) | 0 to 90% RH
– Power Supply: 4-20 mA Loop Powered (8.5 – 36 Vdc)
– Enclosure: PA66
– Format / Mounting: Head Mount